Seismic Fixture Clamp (SFC) Specifications

The AGI seismic fixture clamp (SFC) is fabricated from No. 20 gauge galvanized steel complying with ASTM A653 SS grade 33, with minimum yield and ultimate tensile strenths of 33 ksi (228 MPa) and 45 ksi (310 MPa) respectively.

The SFC is cold formed in several configurations for attachment to different orientations of the light fixture (luminaire) to the main and cross runners of the suspended ceiling system.

.
Part No. Description Quantity

SFC 1

Seismic Fixture Clamp for one standard tapered 2' x 4' light fixture.

4 SFC/set

SFC 1E

Seismic Fixture Clamp for two standard tapered 2' x 4' light fixtures end-to-end. One set of SFC 1 is also required.

2 SFC/set

SFC 1S

Seismic Fixture Clamp for two standard tapered 2' x 4' light fixtures side-by-side. One set of SFC 1 is also required. 2 SFC/set

SFC 1CF

Seismic Fixture Clamp for one standard tapered 2' x 2' light fixture. One set of SFC 1 is also required. 2 SFC/set

SFC 1CFS

Seismic Fixture Clamp for reinforcement of T-Bar main runner joints. 2 SFC/set

AGI SFC models

The different SFC models are used in combination to achieve the patented Unified Ceiling Module benefit for different lighting fixture configurations. Selecting the correct SFC models for your job

SFC Approvals and Listed: Meets the seismic requirements of:
  • City of Los Angeles RR 25653
  • Warnock Hersey (listed)
  • ETL (listed)
  • Conforms to UL 1598
  • Certified to CSA C22.2 No. 250.00 Component only
  • Complies with Acceptance Criteria 184 (AC184) for positive attachment without additional slack wires required
  • IBC 2006 Section 1621
  • UBC 1997 Section 25.213
  • NBC 2006 4.1.9.1.15-19
  • CISCA 0-2 and 3&4
  • ASTM E 580
  • DoD UFC 4-010-01 Blast protection
  • DoD UFC 3-310-04 Seismic Design
  • FEMA 452 Risk Assessment
  • TI-809-04
  • CEC 2002 Section 30-302 Support
  • NEC 2002 Article 410.16 (c) Support

To order Seismic Fixture Clamps (SFCs), contact us to order SFCs

 AGI SFC product family

The lighting fixture is suspended to the ceiling grid by Seismic Fixture Clamps (SFC) at all four corners to ensure that it is earthquake safe.